Anhydrous Ammonia Tank Level Measurement: Top Sensors by Tank Type

Anhydrous Ammonia Tank

Liquid ammonia is anhydrous ammonia that becomes liquid after being pressurized or frozen. Ammonia is an important chemical raw material. For convenient transportation and storage, gaseous ammonia is usually pressurized or cooled to obtain liquid ammonia. Therefore, Anhydrous Ammonia Tank level measurement faces challenges such as low temperature -33.4℃/-28.1 °F, high pressure 0.8~1.5 MPa (116–218 psi), high corrosivity, and high toxicity.

Based on our years of experience in tank level measurement, we recommend three preferred level sensors for Anhydrous Ammonia tank level measurement and control: guided wave radar level transmitters, external ultrasonic level meters, and tuning fork level switches.

Anhydrous Ammonia Tank Types

To select an appropriate liquid level sensor for anhydrous ammonia, it is necessary to identify the common types of anhydrous ammonia tanks. Anhydrous ammonia has a boiling point of -33.5°C and a saturated vapor pressure of 506.62 kPa (at 4.7°C). Based on these physical properties, there are three common types of anhydrous ammonia tanks: fully refrigerated, semi-refrigerated, and fully pressurized.

Fully refrigerated tanks maintain the anhydrous ammonia at a temperature below its boiling point (using a refrigeration circulation system). This keeps the storage pressure at atmospheric levels, allowing for the use of vertical storage tanks, which are suitable for large-scale storage.

Semi-refrigerated tanks typically maintain the storage temperature at approximately 4°C (using a refrigeration circulation system), with an internal pressure ranging from 0.4 to 0.5 MPa.

Fully pressurized tanks store ammonia at ambient temperature; at this temperature, the saturated vapor pressure of ammonia is approximately 1.2 to 1.6 MPa. Storage at ambient temperature is the most common method.

TypesTemperaturePressureCommon Tank Types
Fully refrigerated-33.4 °C (-28.1 °F)Near atmospheric pressureVertical double-walled flat-bottom tank
Semi-refrigeratedApprox. 4 °C (39 °F)0.4–0.5 MPa (58–73 psig)Spherical tank
Fully pressurizedRoom temperature1.2–1.6 MPa (174–232 psig)Horizontal tank, spherical tank

Top 1: Guided-Wave Radar Level Transmitter

Guided wave radar (GWR) level transmitters are a type of radar-based level measurement instrument that utilizes contact-based sensing. It mainly comes in three types: pole type, cable type, and coaxial type. Rod and coaxial types typically have a measurement range of up to 6 meters, while the cable type can reach a maximum range of 30 meters.

GWR level transmitters operate on the principle of Time Domain Reflectometry (TDR). It transmits low-power microwave pulses along a waveguide rod or cable, which are then reflected back when they encounter a liquid surface. The liquid level is calculated by measuring the time interval between the emission of the pulse and the reception of the echo. This measurement method is unaffected by factors such as temperature, pressure, vapors, or foam, ensuring high accuracy and reliability.

Product Specifications for Our Guided Wave Radar Level Transmitters:

Measuring range0–30 m
Accuracy/Resolution±10 mm
output4–20 mA / HART
Power supplyTwo-wire system, 24 V DC (standard: 16–26 V; intrinsically safe: 21.6–26.4 V); four-wire system, 24 V DC or 220 V AC
show4-digit LCD, programmable
process connectionThreaded or flanged, 316L stainless steel
Probe material316L stainless steel or PTFE
sealing materialViton (fluororubber) or Kalrez (perfluoroelastomer)
ShellCast aluminum, plastic, or 316L stainless steel
Explosion proofEx ia IIC T6 Ga; Ex d ia [ia Ga] IIC T6 Gb
Protection levelIP67
Cable entryM20×1.5
Measurement interval/response timeApprox. 1 s
Ambient temperature (working, storage)-40 to 80 °C
Minimum dielectric constant1.3 (when installed in a guided-wave tube)
Process temperature:-40 to 200 °C
Process pressure:-0.1 to 4 MPa

Rod, cable and coaxial probes, ranges up to 30 m. Rated -0.1 to 4 MPa with Ex ia / Ex d approvals and 4–20 mA/HART output. Specify Kalrez seals for ammonia service.

These specifications are fully compatible with fully refrigerated, semi-refrigerated, and fully pressurized Anhydrous ammonia storage tanks. Therefore, guided wave radar level gauges are more advantageous when measuring liquid ammonia, especially in large storage tanks.

In GWR transmitters, the radar signal propagates along a cable, resulting in concentrated energy, a stable signal, high measurement precision, and low operational costs. Compared to other measurement technologies, this approach offers significant advantages, particularly for large storage tanks.

So how should a guided wave radar level transmitter be installed on a liquid ammonia storage tank?

For the installation of liquid ammonia storage tanks, a top flange installation is recommended. However, there are a few points to note during installation:

  1. Install a bracket at the bottom, directly opposite the flange, to secure the cable probe. Prevent the cable from swaying or hitting the wall to ensure accurate liquid ammonia level measurement.
  2. Choosing the right cable length is crucial. It should be calculated based on the distance between the flange and the support bracket. The cable should neither be pulled too taut nor allowed to slacken or curve, as this could compromise measurement accuracy.
  3. When installing the probe assembly of a cable-type guided-wave radar, ensure it is positioned away from inlets, outlets, tank walls, and any internal structures. This helps prevent interference echoes that could affect measurement precision.

If a servo level gauge is used to measure liquid ammonia, the same measurement effect can be achieved, but the cost will be higher.

Top 2: External Ultrasonic Level Meter

If an anhydrous ammonia storage tank is pressurized to liquefy the contents, the interior of the tank is inevitably under high pressure. Drilling a hole in the tank would compromise its seal, creating a risk of leakage. In such cases, the External Ultrasonic Level Meter is an excellent choice.

The External Ultrasonic Level Meter enables true non-contact measurement. Based on the principle of sonar ranging, a specialized ultrasonic probe is mounted on the bottom of the tank’s outer wall. It emits ultrasonic waves that penetrate the tank wall, travel through the liquid inside the tank, reflect off the liquid surface, and are then received by the probe. A specialized algorithm is used to calculate the liquid level height. The probe is completely isolated from the measured medium by the tank wall, eliminating the need to drill holes in the tank. Installation can be performed without interrupting production or draining the tank.

Our External Ultrasonic Level Meter Specifications:

TypeTwo-wire systemFour-wire systemIntrinsically safe
measurable range3m, 5m, 10m, 20m, 30m
Measurement error1‰~1% (too thick tank wall, pressure, and temperature changes can affect accuracy)
display resolution1mm
Measurable wall thickness2~70mm
Power supplyDC24V
Signal outputAnalog output: 4~20mA, maximum load 750Ω
Communication InterfaceRS485/MODBUS/HART communication protocol /
Debug interfaceinfrared
power10w 1w
shellMaterial: cast aluminum alloy
Protection levelIP67
Explosion-proof signsExdllCT6 Gb ExiallB T5Ga
environment humidity15%~100%RH
Host applicable ambient temperature-50℃ to +70℃
Ultrasonic probe operating temperatureNormal Temperature: -50℃~+70℃, high temperature probe temperature can reach 100℃
Host dimensionsLength 160mm* Width 228mm* Height 180mm

Mounted on the outside of the tank bottom, so no drilling and no shutdown. Works through 2–70 mm walls, with ranges up to 30 m.

External ultrasonic level meters can continuously measure liquid levels from outside the tank, allowing for installation without drilling holes in the tank, without open flames, and without interrupting production. The instrument features an explosion-proof design and is widely used in explosive environments. It provides a robust safety barrier for liquid ammonia storage tank projects at chemical plants. This is the definitive advantage of the External Ultrasonic Level Meter.

Of course, the purchase cost of the External Ultrasonic Level Meter is slightly higher than that of other level sensors.

Top 3: Tuning Fork Level Switch

The two types of level sensors described above provide real-time, continuous measurement of liquid ammonia levels. If you also need to control the high and low levels in an anhydrous ammonia storage tank, you can add a tuning fork level switch.

For applications such as high- and low-level alarms, overfill prevention, and low-level pump protection in liquid ammonia storage tanks, the tuning fork level switch can serve as a standalone point-level detection sensor. The tuning fork detects the presence of liquid at the measurement location by monitoring changes in its vibration state and can output an independent digital signal.

TemperatureMedium temperature-20℃~+220℃
Ambient temperature-40℃~+70℃
Storage temperature-40℃~+85℃
Ambient humidity≤95%RH
Measured mediaLiquid, powder or granular solid
Medium densitySolid ≥ 0.1g/cm³
Liquid ≥ 0.6g/cm³
Solid particles< 10 mm
Liquid viscosity<1000mm2/s
Angle of repose≥200
Pressure Range-0.1~+4.0MPa
MaterialShell MaterialDie cast aluminum alloy
Fork materialS304, S316
Connection methodThreadG1/2”, G3/4”, G1”, Customized
FlangeCustomer defined
Sanitary chuck50.5mm, Customized
Supply VoltageDC24V AC220V 50Hz
OutputRelay outputLoad AC250V/4A DC60V/4A
Open collector (NPN) outputLoad 400mA
Open collector (NPN) outputLoad 400mA
Power consumptionAC power supply3W Max
DC power supply5W Max
Electrical interfaceM20*1.5
Protection levelIP65
Explosion-proof levelExdIIBT1~6 ExdIICT1~6
Action time3S
VibrationTuning fork vibration frequency300±50Hz
Environmental vibration levelV.L.4 Acceleration no greater than 1 g

Independent high/low level alarm and overfill protection. Rated -0.1 to 4 MPa, with relay or NPN output and Ex d housing.

Therefore, by considering the tank’s temperature, pressure, internal structure, and the requirements for continuous measurement and liquid level alarms, we can select the most suitable anhydrous ammonia tank level measurement solution.

How to Choose

We have compiled a simple summary for your reference:

TypesFully refrigerated (-33.4 °C / -28.1 °F, near atmospheric pressure)Semi-refrigerated (approx. 4 °C / 39 °F, 0.4–0.5 MPa / 58–73 psig)Full pressure (ambient temperature, 1.2–1.6 MPa / 174–232 psig)Opening RequirementsProcurement cost
Guided-wave radar level transmitterApplicable; not suitable when tank height exceeds cable length (approx. 30 m)Suitable; preferred optionUsable, preferred; requires an airtight seal—Viton seals are not suitableOne connection point on the tank topModerate, depending on pressure and range
Externally mounted ultrasonic level meterNot applicable, due to obstruction by the thermal insulation layerApplicable for spherical and horizontal tanksUsableNo openings requiredRelatively high
Tuning fork level switchApplicableSuitableUsableOne connection point on the tank top or tank sideLow

FAQ

At Sino-Inst, we believe that guided-wave radar level transmitters are the preferred level sensors for anhydrous ammonia tanks. Guided-wave radar level transmitters feature mature measurement technology, and their specifications fully cover the requirements of the vast majority of anhydrous ammonia tanks. Of course, if there are special requirements, other level sensors may also be considered.

Yes, it can. However, an 80G high-frequency radar level transmitter must be selected. Liquid ammonia is a medium with a low dielectric constant (εr ≈ 1.3), resulting in weak radar wave reflections that are prone to attenuation or distortion.

At the same time, a low-temperature vapor layer or mist can easily form inside the tank; as pressure increases, the density of the vapor rises, further exacerbating signal attenuation. This requires the radar to be equipped with a high-gain antenna and intelligent echo processing algorithms capable of penetrating the vapor layer, precisely locking onto the liquid surface reflection signal, and filtering out false echoes.

This is primarily due to the complex conditions inside ammonia storage tanks. Liquid ammonia is highly volatile, forming a high-concentration vapor layer above the liquid surface. Since the speed of sound in gas differs from that in air (and varies with concentration), ultrasonic waves experience severe speed-of-sound distortion when passing through the vapor layer, resulting in low or wildly fluctuating measurements.

Yes. You can use a dual-flange differential pressure transmitter to measure the liquid level in an ammonia storage tank. However, the calculation depends on the density of the medium. When changes in the temperature, pressure, or composition of liquid ammonia cause density variations, appropriate compensation must be applied.

For non-refrigerated anhydrous ammonia tanks, the filling level generally should not exceed approximately 85% of the tank’s water volume. U.S. OSHA 29 CFR 1910.111 stipulates: For above-ground, uninsulated tanks, the maximum filling level is 82% by volume (up to 87.5% when the liquid ammonia temperature is not less than 30 °F); 83.5% for above-ground insulated tanks, and 85% for underground tanks. The reserved vapor space is used to accommodate the thermal expansion of the liquid. Refrigerated tanks must not be completely filled with liquid at the temperature corresponding to the safety valve’s opening pressure.

We recommend installing a guided-wave radar level transmitter for refrigerated ammonia tanks. Of course, specific tank parameters are required to confirm this.

For anhydrous ammonia storage tanks that require both continuous level monitoring and safety level control, a configuration combining a continuous level transmitter and a tuning-fork level switch can be used. The continuous level transmitter handles level display and trend monitoring, while the tuning-fork level switch provides critical high- and low-level protection, ensuring that process measurement and safety interlocks remain relatively independent.

In addition to the three types of sensors recommended in this article for anhydrous ammonia storage tank level measurement and control, other types of level sensors may also be selected based on specific parameters. Examples include dual-flange differential pressure level transmitters, 80G radar level transmitters, or magnetic flip-plate level gauges. Each has its own measurement advantages and operational limitations.

If you are still unsure which anhydrous ammonia level measurement solution to choose, please feel free to contact our sales engineers for consultation at any time.